SYN-7 Synchroniser Relay

back
The synchroniser relay SYN-7 adjusts voltage and frequency of a generator to the mains, in order to connect it at a minimum difference of frequency and voltage, and at the same phase position. Depending on its configuration, the SYN-7 is monitoring sense of rotation, voltage difference and asymmetry. Voltage measurement is done as 2-, 3- or 4- wire measurement, according to the preset parameterisation. The frequency measurement generally is on L1 and L2. In island mode, the desired frequency and voltage are internally set by the device. A separate variant of the SYN-7 is available for measuring voltages <= 100 V.

Downloads


pdf data sheet (english)

pdf description (english)

pdf data sheet (german)

pdf description (german)

pdf software

Technical Data

Auxiliary Voltage
24V DC (18 ... 36 V)
optionally 230V AC / 12 V DC

Power Consumption
approx. 4 W at 24 V DC,
approx. 6 VA at 230 V AC

Digital Inputs
LowActive
(Contact Voltage 12 V, 5 mA,
opto-decoupled), accord. to DIN

Relay Outputs
230 V / 50 Hz / 2 A (potential-free)

Analogue Outputs
0/2 ... 10 V +/- 0.05 V max. 10,5 V

Measuring Range
approx. 50 up to 230 / 400 V,
tolerance < 0,5 % of full scale
(270 / 480 V)

Frequency Measurement
35.0 Hz up to 65.0 Hz
about approx. 50 V L-N +/- 0.05 Hz

Leading Time
adjustable 50 ... 500 ms

Adjustment Pulses
adjustable 0.1 s up to 100 s

Max. Frequency Difference
adjustable 0.1 ... 1.0 Hz

Max. Voltage Difference
adjustable 1 ... 15 %

Climatic Conditions
acc. to DIN EN 60204-1 ( 05-2010 )
Ambient Temperature
operation:              -20 ... +55 °C
transport/storage:  -25 ... +55 °C

Housing Dimensions
W / H / D 100 x 75 x 110 mm
DIN top-hat rail mounting 35 mm


Ordering Information:

SYN-7 / 230V AC:            E1358
SYN-7 / 24V DC:              E1359
SYN-7 / 100V / 230V AC: E1657
SYN-7 / 100V / 24V DC:   E1658